QuickOPC Compatibility Test List for PubSub: Difference between revisions
From OPC Labs Knowledge Base
Line 176: | Line 176: | ||
|<span style='color:green'>Passed</span> | |<span style='color:green'>Passed</span> | ||
|<ref name="securitynottested"/><ref name="udpunicast"/> | |<ref name="securitynottested"/><ref name="udpunicast"/> | ||
|- | |||
|'''Hilscher: LFW-IoT / OPC UA Server and PubSub (NRPEB H90-RE)''' | |||
|? | |||
|2023-10 | |||
|OPC Labs | |||
|2023.2 Alpha | |||
|Interoperability workshop | |||
|<span style='color:green'>Passed</span> | |||
|<ref>20 ms</ref> | |||
|- | |- |
Revision as of 10:57, 10 October 2023
See also: QuickOPC Compatibility Test List (for Client/Server)
Introduction
See Compatibility Test Lists - Concepts.
Platform Hardware
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
PC, Intel Core i7-8550U CPU @ 1.80 GHz 1.99 GHz; 16.0 GB | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | W10/x64 | |
Raspberry Pi Model 4; 4 GB | 2021-01 | OPC Labs | 2021.1 (5.60) | Basic test | Passed | Raspbery Pi OS |
More tests were performed, currently not explicitly listed here.
Operating Systems
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Microsoft Windows 10 Pro | 1803 x64 (English) | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | |
21H1 x64 (English) | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | ||
22H2 x64 (English) | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | ||
Raspberry Pi OS with desktop | 2021-01-11 | 2021-01 | OPC Labs | 2021.1 (5.60) | Basic test | Passed |
More tests were performed, currently not explicitly listed here.
.NET Runtimes
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
.NET Framework | 4.7.2 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | |
.NET | 5.0.2 | 2021-01 | OPC Labs | 2021.1 (5.60.0.13) | Basic test | Passed |
More tests were performed, currently not explicitly listed here.
OPC Publishers
UADP Messages over UDP Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [1] |
Hilscher: LFW-IoT / OPC UA Server and PubSub | V1.0.1.0 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [2][3][4] |
? | 2022-10 | OPC Labs | 2022.2 Alpha | Interoperability workshop | Passed | [2][3] | |
Hilscher: LFW-IoT / OPC UA Server and PubSub (NRPEB H90-RE) | ? | 2023-10 | OPC Labs | 2023.2 Alpha | Interoperability workshop | Passed | [5] |
Phoenix Contact: PLCnext | 2022.0 beta | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [2] |
Prosys OPC: OPC UA Java SDK | 4.6.1-beta | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [2][3][6][7] |
Softing Industrial Automation: dataFEED OPC UA .NET Standard PubSub SDK | 2.2 | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | [8][9] |
Unified Automation: C++ based OPC UA Server SDK WINDOWS | 1.8.0 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | [10] |
Unified Automation: High Performance OPC UA SDK 1.7.1 | 1.7.1 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | [10] |
Yokogawa Electric Corporation: UA Server for CENTUM VP | R1.05.00 | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | [9] |
JSON Messages over MQTT Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TwinCAT | 4025.3 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | |
ICONICS GENESIS64 | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [11][12][13] |
Siemens AG: internal | 0.0.1 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | [14][15] |
Softing Industrial Automation: dataFEED OPC UA .NET Standard Server SDK | 3.0 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [8] |
UADP Messages over MQTT Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Softing Industrial Automation: dataFEED OPC UA .NET Standard Server SDK | 3.0 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [8] |
OPC Subscribers
Subscribers were tested with messages published by the UADemoPublisher.
UADP Messages over UDP Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [16] |
Hilscher: LFW-IoT / OPC UA Server and PubSub (NXHX 90-JTAG) | V1.0.1.0 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [2][3][4] |
JSON Messages over MQTT Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
ICONICS GENESIS64 | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [13] |
More tests were performed, currently not explicitly listed here.
PubSub Configuration Model
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Warning | [17][18] |
Hilscher: LFW-IoT / OPC UA Server and PubSub (NRPEB H90-RE) | ? | 2023-10 | OPC Labs | 2023.2 Alpha | Interoperability workshop | Passed | |
Phoenix Contact: PLCnext | 2022.0 beta | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | |
Siemens AG: internal | 0.0.1 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | [14] |
Softing Industrial Automation: OPC UA C++ Server Development Toolkits for Windows | ? | 2019-07 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | |
Softing Industrial Automation: dataFEED OPC UA .NET Standard Server SDK | 3.0 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Warning | [19] |
Unified Automation: C++ based OPC UA Server SDK WINDOWS | 1.8.0 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed | |
Unified Automation: High Performance OPC UA SDK 1.7.1 | 1.7.1 | 2023-03 | OPC Labs | 2023.1 Alpha | Interoperability workshop | Passed |
More tests were performed, currently not explicitly listed here.
Security Key Service
- ↑ Tests included chunked and secured messages (static keys).
- ↑ 2.0 2.1 2.2 2.3 2.4 Security not tested.
- ↑ 3.0 3.1 3.2 3.3 Tested UDP unicast.
- ↑ 4.0 4.1 Tested RawData encoding.
- ↑ 20 ms
- ↑ Tested delta frames.
- ↑ Tested events.
- ↑ 8.0 8.1 8.2 Subscriber UADP Periodic Fixed Layout Facet
- ↑ 9.0 9.1 Subscriber UADP Flexible Layout Facet
- ↑ 10.0 10.1 Including security
- ↑ MessageId is published as an integer, not a GUID.
- ↑ DataSetWriterId is published as a GUID, not a UInt16.
- ↑ 13.0 13.1 Capable of single message format only: NetworkMessageHeader == 1, DataSetMessageHeader == 1, SingleDataSetMessage == 0. Dataset fields are only encoded as in DataValue representation.
- ↑ 14.0 14.1 Internal project consisting of an OPC UA Server+Publisher, Mosquitto, and a dynamic Web page with the data. Source correlation: {2F4CBEFC-A71B-4628-B723-A00DB63EDB8D}
- ↑ Tested MQTT version 3 and 5.
- ↑ A single simple test, with DataValue encoding.
- ↑ Publishing interval not properly exposed.
- ↑ Maximum string length not properly exposed.
- ↑ TransportSettings under PubSub connections and writer groups can be of abstract type.