QuickOPC Compatibility Test List for PubSub
From OPC Labs Knowledge Base
See also: QuickOPC Compatibility Test List (for Client/Server)
Introduction
See Compatibility Test Lists - Concepts.
Platform Hardware
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
PC, Intel Core i7-8550U CPU @ 1.80 GHz 1.99 GHz; 16.0 GB | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | W10/x64 | |
Raspberry Pi Model 4; 4 GB | 2021-01 | OPC Labs | 2021.1 (5.60) | Basic test | Passed | Raspbery Pi OS |
More tests were performed, currently not explicitly listed here.
Operating Systems
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Microsoft Windows 10 Pro | 1803 x64 (English) | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | |
Microsoft Windows 10 Pro | 21H1 x64 (English) | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | |
Raspberry Pi OS with desktop | 2021-01-11 | 2021-01 | OPC Labs | 2021.1 (5.60) | Basic test | Passed |
More tests were performed, currently not explicitly listed here.
.NET Runtimes
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
.NET | 5.0.2 | 2021-01 | OPC Labs | 2021.1 (5.60.0.13) | Basic test | Passed |
More tests were performed, currently not explicitly listed here.
OPC Publishers
UADP Messages over UDP Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [1] |
Phoenix Contact: PLCnext | 2022.0 beta | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | [2] |
Softing Industrial Automation: dataFEED OPC UA .NET Standard PubSub SDK | 2.2 | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | [3][4] |
Yokogawa Electric Corporation: UA Server for CENTUM VP | R1.05.00 | 2019-07 | OPC Labs | 2019.1 (5.55.0.3) | Interoperability workshop | Passed | [4] |
JSON Messages over MQTT Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TwinCAT | 4025.3 | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | |
ICONICS GENESIS64 | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [5][6][7] |
OPC Subscribers
Subscribers were tested with messages published by the UADemoPublisher.
UADP Messages over UDP Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [8] |
JSON Messages over MQTT Transport
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
ICONICS GENESIS64 | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed | [7] |
More tests were performed, currently not explicitly listed here.
PubSub Configuration Model
Other system model | Other system version | Test date | Performed by | This product version | Test type | Test outcome | Notes |
---|---|---|---|---|---|---|---|
Beckhoff Automation: TF6100 | TwinCAT 3 OPC UA | ? | 2021-04 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Warning | [9][10] |
Phoenix Contact: PLCnext | 2022.0 beta | 2021-10 | OPC Labs | 2021.3 Alpha | Interoperability workshop | Passed | |
Softing Industrial Automation: OPC UA C++ Server Development Toolkits for Windows | ? | 2019-07 | OPC Labs | 2021.2 (5.61.0.6) | Interoperability workshop | Passed |
More tests were performed, currently not explicitly listed here.
Security Key Service
- ↑ Tests included chunked and secured messages (static keys).
- ↑ Security not tested.
- ↑ Subscriber UADP Periodic Fixed Layout Facet
- ↑ 4.0 4.1 Subscriber UADP Flexible Layout Facet
- ↑ MessageId is published as an integer, not a GUID.
- ↑ DataSetWriterId is published as a GUID, not a UInt16.
- ↑ 7.0 7.1 Capable of single message format only: NetworkMessageHeader == 1, DataSetMessageHeader == 1, SingleDataSetMessage == 0. Dataset fields are only encoded as in DataValue representation.
- ↑ A single simple test, with DataValue encoding.
- ↑ Publishing interval not properly exposed.
- ↑ Maximum string length not properly exposed.