Application note: QuickOPC-UA Compatibility Test List
Last updated: November 2014
<style> </style>
Introduction
The Compatibility Test List documents the test performed with the product with the aim to assure its compatibility widest range of systems it depends on or interoperates with. This document is updated from time to time, as new tests are being performed.
This document is grouped by the classes of systems that this product depends on or interoperates with, such as “Platform Hardware” or “Operating Systems”. Each class has a standalone chapter.
The entries in each group are sorted by the columns from left to right, i.e. first by “Other System Model”, then by “Other System Version”, and then by “Test Date”.
Field Descriptions
Other System Model
“Other system” is the system we are testing the compatibility of this product with. It can be hardware, software, or a combination.
Other System Version
This field contains additional details about the other system, typically its versioning information, if available.
Test Date
Describes when the test was performed. It can be a specific date, date range, or approximate date such as a month in a year.
Performed By
This field determines the entity (person or organization) that has performed the test.
This Product Version
This field contains versioning information about this (our) product, typically including the software build and revision numbers, too.
If a test that was otherwise identical in other parameters has been performed with a newer version of this product, and the outcome was the same or better, the old entry in the compatibility test list may be removed for brevity. This is done so because the main purpose of the compatibility test list is to assess the compatibility of the latest available version of this product.
On the other hand, entries for tests performed with earlier versions of this product that were not repeated later are always retained. It can be assumed that later versions of this product continue to operate with at least the same outcome as the version that has been tested.
Test Type
- Alpha Test.
- Basic Test.
- Compliance Test.
- Developer Test.
- Field Test.
- Interoperability Workshop.
Test Outcome
- Failed. There is always a Note describing the details.
- Inconclusive. There is always a Note describing the details.
- Passed.
- Warning. There is always a Note describing the details.
Notes
This field contains any relevant notes, especially to the test environment, or outcome of the test.
Platform hardware
Other System Model |
Other System Version |
Test Date |
Performed By |
This Product Version |
Test Type |
Test Outcome |
Notes |
Intel Core 2 CPU T5600, 1.83 GHz, 2 GB RAM |
|
2011-09 |
OPC Labs |
1.00.395.1 |
Developer Test |
Passed |
WXP SP3 |
Intel Core 2 Quad CPU Q6600, 2.40 GHz, 4 GB RAM |
|
2011-09 |
OPC Labs |
1.00.395.1 |
Developer Test |
Passed |
W7/x86 |
Intel Xeon CPU, E5420 @2.50 GHz (2 processors), 1 GB RAM |
vm |
2010-09-27 |
OPC Labs |
1.00.395.1 |
Basic Test |
Passed |
WS2003 SP2/x86 |
Intel Xeon CPU, E5420 @2.50 GHz (2 processors), 2 GB RAM |
vm |
2010-09-27 |
OPC Labs |
1.00.395.1 |
Basic Test |
Passed |
WS2008 SP1/x86 |
More tests were performed, currently not explicitly listed here. |
Operating Systems
Other System Model |
Other System Version |
Test Date |
Performed By |
This Product Version |
Test Type |
Test Outcome |
Notes |
Microsoft Windows XP Professional |
SP3 (English) |
2011-09 |
OPC Labs |
1.00.395.1 |
Developer Test |
Passed |
|
Microsoft Windows Server 2003 R2 Standard Edition |
x86 SP2 (English) |
2010-09-27 |
OPC Labs |
1.00.395.1 |
Basic Test |
Passed |
|
Microsoft Windows Server 2008 Standard Edition |
x86 SP1 (English) |
2010-09-27 |
OPC Labs |
1.00.395.1 |
Basic Test |
Passed |
|
Microsoft Windows 7 Enterprise |
x86 (English) |
2011-09 |
OPC Labs |
1.00.395.1 |
Developer Test |
Passed |
|
More tests were performed, currently not explicitly listed here. |
OPC Servers
Other System Model |
Other System Version |
Test Date |
Performed By |
This Product Version |
Test Type |
Test Outcome |
Notes |
3S-Smart Software Solution: CODESYS OPC UA Server |
as of test date |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Bachmann electronic: M1 OPC UA Server |
V1.00.02 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Warning |
see 1) |
Beckhoff Automation: TF 6100 OPC-UA |
2.0.0.8 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
2.0.0.63 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Beckhoff Automation: TF 6100 OPC-UA (CE-ARM) |
2.0.0.63 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Beckhoff Automation: TwinCAT OPC UA Server |
1.6.68 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.6.88 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
Beckhoff Automation: TwinCAT OPC UA Server CE |
1.6.68 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.6.88 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
Bosch Rexroth Electric Drives and Control: IndraMotion MTX |
12.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
Bosch Rexroth: IndraControl MLC |
14VRS |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Bosch Rexroth: IndraControl MLC L65 |
13V04 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Warning |
see 11) |
13VRS |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
Bosch Rexroth: IndraControl MTX |
14VRS |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
COPA-DATA: zenon Product Family |
7.50.9999 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
7.50.15647 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
COPA-DATA: zenon Logic |
7.50.15647 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
ETM professional control: WinCC OA OPC UA Server |
3.10 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
Fox-IT: Fox OPC UA Replicator |
1.0.0 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Fraunhofer IOSB: DigET Middleware Server |
as of test date |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
Fraunhofer IOSB: ProVis.Agent |
as of test date |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
as of test date |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
2.10.18 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Fraunhofer IOSB: SecurePlugAndWorkUAServer |
1.1.1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Fraunhofer IOSB: SkillProUAServer |
1.0.2 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
GE Energy: SR350 |
v2.00 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
GE Energy: SR850 |
as of test date |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
GE Intelligent Platforms: Proficy GDS |
1.00 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
HB-Softsolution: OPC UA Java SDK Server |
0.1 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Warning |
see 1) |
ICONICS: GENESIS64 |
10.72.087.02 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
ICONICS: Hyper Historian |
10.72.087.02 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Warning |
see 9) |
Inductive Automation: OPC-UA SDK |
0.2.0-SNAPSHOT |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
KW-Software: PC OPC UA Standalone Server |
Step 1 beta Build 570 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
KW-Software: OPC UA Server on ACX 3050 |
1.0.570 beta |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
MatrikonOPC: Industrial UA Modbus Gateway |
2.0.5 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
MatrikonOPC: OPC-UA Embedded Server SDK – Embedded Server Profile Configuration |
2.0.5 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
MatrikonOPC: OPC-UA Embedded Server SDK – Micro Embedded Server Profile Configuration |
2.0.5 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
MatrikonOPC: OPC-UA Embedded Server SDK – Nano Embedded Server Profile Configuration |
2.0.5 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
MatrikonOPC: Universal Connectivity Server |
2.1.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
MatrikonOPC: UA Wrapper for COM OPC Servers |
1.2.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Warning |
see 2) |
MSIndustrie Software: MSI-UA-Server |
1.0.0.2 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.0.0.3 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
OPC Foundation: OPC UA COM Wrapper |
1.01.332.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
OPC Foundation: UA Micro Server (Linux/Debian) |
1.0.0.1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
OPC Foundation: UA Nano Server (Linux/Debian) |
1.0.0.1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Progea: Movicon.NExT |
12.0 (Beta) |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Warning |
see 3), 10) |
12.0 (RC) |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
12.0.8 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
Prosys PMS: Prosys OPC UA Java SDK |
1.2.2 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.4.0 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
1.4.6 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Warning |
see 12) |
|
2.0 BETA |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
2.0.2 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Prosys PMS: Prosys OPC UA Simulation Server |
2.0 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Prosys PMS: Prosys OPC UA Historian |
0.9 BETA |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Quintec Datentechnik: Siemens WinCC Runtime Advanced |
V13SP1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Siemens: miniweb OPC UA |
4.2.1 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
4.4.0 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
4.6.2+ |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Siemens: OPC UA Server for WinCC |
1.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
Siemens: SIMATIC NET OPC Servers |
V8.1 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
V8.2 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
Siemens: SIMATIC NET OPC Server S7 |
V12 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
Siemens: SIMATIC NET OPC Server S7 opt |
V13 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Siemens: SIMATIC SIPAT OPC UA ADI SDK |
1.02 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Warning |
see 5) |
Siemens: Simatic WinCC |
V7.2 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
V7.3 SE |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Siemens: SIMOCODE pro V PN |
V0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Failed |
see 4) |
Siemens: SPPA-T3000 OPC UA Server |
70.1.04 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
07.3.03.00 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Siemens: WinCC Runtime Professional |
V12.0 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
V13 SP1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Softing Industrial Automation: OPC Toolbox UA Server for Windows |
5.10 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
5.20 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Warning |
see 7) |
|
5.30 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
Softing Industrial Automation: OPC UA .NET SDK Server |
1.10 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
1.11 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
Softing Industrial Automation: OPC UA .NET Server Development Toolkits |
1.26 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Softing Industrial Automation: OPC UA C++ Server Development Toolkit for Linux |
5.35 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Softing Industrial Automation: OPC UA C++ Server Development Toolkit for Windows |
5.35 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
TerxaSoft: Visual OPC Server .NET |
3.1 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
Unified Automation: .NET based OPC UA Server SDK |
2.1 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
2.3.1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Unified Automation: ANSI C based OPC UA Server SDK |
1.2.1 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.3.0 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
1.4.0 |
2013-09 |
OPC Labs |
5.23.385.1 |
Interoperability Workshop |
Passed |
|
|
1.4.1 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Unified Automation: C++ based OPC UA Server SDK Windows |
1.3.0 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Passed |
|
1.3.2 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
1.4.2 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
|
Unified Automation: UA gateway – connect classic OPC |
1.2 |
2011-09 |
OPC Labs |
1.00.395.1 |
Interoperability Workshop |
Warning |
see 6) |
1.3.0 |
2012-10 |
OPC Labs |
5.21.441.1 |
Interoperability Workshop |
Passed |
|
|
1.3.5 |
2014-11 |
OPC Labs |
5.32.475.1 |
Basic Test |
Passed |
|
Note 1: (array) index ranges are ignored
Note 2: absolute deadband filter gave BadFilterNotAllowed error
Note 3: Security mode other than None gave BadSecureChannelClosed
Note 4: connectivity unreliable
Note 5: (array) index ranges are ignored with Subscriptions
Note 6: absolute deadband ignored
Note 9: absolute deadband filter gave returns BadMonitoredItemFilterUnsupported error
Note 10: username/password authentication required for writes but was not supported by client at the time of the test
Note 11: many diagnostic objects return null
Note 12: GetEndpoints returns no discovery URIs with endpoints