QuickOPC Compatibility Test List

From OPC Labs Knowledge Base
Jump to navigation Jump to search

Older test lists: Application note: QuickOPC-UA Compatibility Test List

Introduction

See Compatibility Test Lists - Concepts.

Platform Hardware

Other system model Other system version Test date Performed by This product version Test type Test outcome Notes
PC, Intel Core2 Quad CPU Q6600 @ 2.40 GHz 2.39 GHz; 4.00 GB 2018-06 OPC Labs 2018.2 (5.53) Basic test Passed W7SP1/x32
PC, Intel Core i7-3930K CPU @ 3.20 GHz 3.80 GHz; 32.0 GB 2015-11 OPC Labs 5.36 Interoperability workshop Passed W7SP1/x64
PC, Intel Core i7-3930K CPU @ 3.20 GHz 3.80 GHz; 32.0 GB 2016-11 OPC Labs 5.41 Interoperability workshop Passed W7SP1/x64
PC, Intel Core i7-3930K CPU @ 3.20 GHz 3.80 GHz; 32.0 GB 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed W7SP1/x64
PC, Intel Core i7-7820X CPU @ 3.60 GHz 3.60 GHz; 32.0 GB 2018-06 OPC Labs 2018.3 (5.54) Developer test Passed W10/x64
PC, Intel Core i7-8550U CPU @ 1.80 GHz 1.99 GHz; 16.0 GB 2019-03 OPC Labs 2019.1 (5.55) Interoperability workshop Passed W10/x64
Raspberry Pi Model 4; 4 GB 2021-01 OPC Labs 2021.1 (5.60) Basic test Passed Raspbery Pi OS

More tests were performed, currently not explicitly listed here.

Operating Systems

Other system model Other system version Test date Performed by This product version Test type Test outcome Notes
CentOS 7.5.1804 2018-07 OPC Labs 2018.3 (5.54) Basic test Passed RID: centos.7-x64
Microsoft Windows 7 Enterprise SP1, x64 (English) 2015-11 OPC Labs 5.36 Interoperability workshop Passed
Microsoft Windows 7 Enterprise SP1, x32 (English) 2018-06 OPC Labs 2018.2 (5.53) Basic test Passed
Microsoft Windows 7 Enterprise SP1, x64 (English) 2016-11 OPC Labs 5.41 Interoperability workshop Passed
Microsoft Windows 7 Enterprise SP1, x64 (English) 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Microsoft Windows 10 Pro 1803, x64 (English) 2018-06 OPC Labs 2018.3 (5.54) Developer test Passed RID: win10-x64
Microsoft Windows 10 Pro 1803, x64 (English) 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Microsoft Windows 10 Pro 1903, x64 (English) 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed
Microsoft Windows 10 Pro 1903, x86 (English) 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed
Microsoft Windows Server 2019 Datacenter 1809 (Aug 2019), x64 (English) 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed
Oracle Linux 7.5 2018-07 OPC Labs 2018.3 (5.54) Basic test Passed RID: linux-x64
Red Hat Enterprise Linux 7.4 2018-06 OPC Labs 2018.3 (5.54) Basic test Passed RID: rhel.7-x64
Ubuntu 17.10 2018-06 OPC Labs 2018.3 (5.54) Basic test Passed RID: linux-x64
Ubuntu 18.04 2018-06 OPC Labs 2018.3 (5.54) Basic test Passed RID: ubuntu.18.04-x64
Raspberry Pi OS with desktop 2021-01-11 2021-1 OPC Labs 2021.1 (5.60) Basic test Passed

More tests were performed, currently not explicitly listed here.

.NET Runtimes

Other system model Other system version Test date Performed by This product version Test type Test outcome Notes
.NET Core 2.0.6 2018-06 OPC Labs 2018.3 (5.54) Basic test Passed
.NET Core 2.0.7 2018-06 OPC Labs 2018.3 (5.54) Basic test Passed
.NET Core 2.1.2 2018-07 OPC Labs 2018.3 (5.54) Basic test Passed
.NET Core 2.1.6 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed
.NET Core 2.1.12 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed
.NET Framework 4.7 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed
.NET Framework 4.8 2019-08 OPC Labs 2019.1 (5.55.0.12) Basic test Passed

More tests were performed, currently not explicitly listed here.

OPC Servers

OPC UA Generic/Data

Other system model Other system version Test date Performed by This product version Test type Test outcome Notes
3S-Smart Software Solutions: CODESYS OPC UA Server 2015-11 OPC Labs 5.36 Interoperability workshop Passed
3S-Smart Software Solutions: CODESYS OPC-UA Server V3.5.13.10 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
Baker Hughes/GE: iFIX 6.0 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
Beckhoff Automation: TF6100 OPC-UA 2.2.21 2015-11 OPC Labs 5.36 Interoperability workshop Passed
Beckhoff Automation: TwinCAT TF6100 OPC UA (Client/Server) 3.x 2016-11 OPC Labs 5.41 Interoperability workshop Passed
Bosch Rexroth: IndraMotion MTX 14VRS 2015-11 OPC Labs 5.36 Interoperability workshop Warning [1]
Certec EDV: atvise 3.3.0 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
dieEntwickler Elektronik: SITOP PSU8600 1.2.0-Dev 2016-11 OPC Labs 5.41 Interoperability workshop Failed [2]
Fraunhofer-Gesellschaft: ProVis.Agent 2.15.14 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed
Fraunhofer-Gesellschaft: SecurePlugAndWorkUAServer 1.1.3 2016-11 OPC Labs 5.41 Interoperability workshop Passed
General Electric Corporation: CIMPLICITY OPC UA Server 9.5 Beta 2015-11 OPC Labs 5.36 Interoperability workshop Passed [3]
General Electric Corporation: CIMPLICITY Server 9.5 SIM2 2016-11 OPC Labs 5.41 Interoperability workshop Warning [4]
Hilscher: OPC UA Server Micro 0.9.11.1 2016-11 OPC Labs 5.41 Interoperability workshop Warning [5]
Hilscher: OPC UA Server Nano 0.9.11.1 2016-11 OPC Labs 5.41 Interoperability workshop Warning [5]
HIMA Paul Hildebrandt: HIMA OPCUA Server 1.0 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed [6]
HMS Industrial Networks: eWON Flexy FW 13.1PR 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
Honeywell: ControlEdge PLC R152 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Honeywell: Experion PKS OPC UA DA/HDA Server 2020-03 OPC Labs 2020.2 (5.58.0.2) Interoperability workshop Passed [7][8]
IBHsoftec: IBH Link UA 3.07 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed [9]
IBHsoftec: IBH OPC UA IOT2040 3.07 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed [9]
ICONICS: GENESIS64 10.96 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Warning [10][11]
Inductive Automation: Eclipse Milo OPC-UA Server SDK 0.1.0-SNAPSHOT 2016-11 OPC Labs 5.41 Interoperability workshop Passed [12]
Inductive Automation: Eclipse Milo OPC-UA Server SDK 0.3.0-SNAPSHOT 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Inductive Automation: Ignition OPC-UA Server 8.0 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
IPCOMM: ipConvLite 3.x 2015-11 OPC Labs 5.36 Interoperability workshop Passed
IPCOMM: ipConvOPC 3.x 2015-11 OPC Labs 5.36 Interoperability workshop Passed
Kepware Technologies: Kepware Edge[13] Beta 6.7 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Kepware Technologies: OPC UA Server - KEPServerEX 6.0 2016-11 OPC Labs 5.41 Interoperability workshop Passed
MatrikonOPC: FLEX OPC UA SDK - Embedded Server Profile R410.3 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
MatrikonOPC: FLEX OPC UA SDK - Micro Embedded Device Server Profile R410.3 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
MatrikonOPC: FLEX OPC UA SDK - Nano Embedded Device Server Profile R410.2 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
MatrikonOPC: FLEX OPC UA SDK - Standard Server Profile R410.3 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Microsoft: .Net Standard Library OPC Server Nov-11-2016 2016-11 OPC Labs 5.41 Interoperability workshop Warning [14]
Microsoft: .Net Standard Reference Server (Ubuntu) Sep-18-2017 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Microsoft: .Net Standard GDS Server Sep-18-2017 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
OMRON: NJ OPC UA Server 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed [9]
Phoenix Contact: PC WORX UA Server 1.03.961.3 2015-11 OPC Labs 5.36 Interoperability workshop Warning [15]
Progea: Platform.NExT 3.3.200 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Progea: Connext 3.3.200 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Prosys OPC: OPC UA Java SDK 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Warning [16]
Prosys OPC: Sentrol - OPC UA SDK for Delphi 7.0 Beta 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Failed [17]
Real Time Automation: Royalty-Free ANSI C OPC UA Server Stack, Toolkit & SDK 1.0 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Rockwell Automation: FactoryTalkLinxGateway 6.10 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Warning [18]
SAP SE: Plant Connectivity on Linux (Raspbian) 15.1.5 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed [19]
SAP SE: Plant Connectivity on Windows 10 15.1.5 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed [19]
Schneider Electric: InduSoft IoTView OPC UA Server (Linux) v8.1 SP3 2018-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Schneider Electric: Indusoft Web Studio OPC UA Server v8.1 SP3 2018-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Siemens: miniweb OPC UA 5.3.2 beta 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Failed [20]
Siemens: SIMATIC CPU 1516-3 PN/DP V2.6 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed [21]
Siemens: SIMATIC NET OPC Server S7 opt V13 SP1 2015-11 OPC Labs 5.36 Interoperability workshop Warning [22]
Siemens: SIMATIC RF100 V1.1 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Warning [23]
Siemens: SIMATIC RF600 V3.1 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
Siemens: SIMATIC S7-1518[24] V2.5 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Siemens: Simatic WinCC V7.4 2015-11 OPC Labs 5.36 Interoperability workshop Passed [25]
Siemens: Simatic WinCC V7.5 2018-10 OPC Labs 5.54 (2018.3.0.33) Interoperability workshop Passed [25]
Siemens: WinCC Runtime Professional V15.1 2018-10 OPC Labs 5.54 (2018.3.0.33) Interoperability workshop Passed
Softing Industrial Automation: dataFEED OPC SIS 1.12 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed
Softing Industrial Automation: dataFEED OPC Suite 4.43.0 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Warning [26]
Softing Industrial Automation: dataFEED OPC UA .NET Standard Server SDK 2.2 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed
Softing Industrial Automation: Falcon Server[27] 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Warning [28]
Softing Industrial Automation: OPC UA C++ Server Development Toolkits for Windows 1.00 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Softing Industrial Automation: OPC UA Embedded Toolkit 5.53 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Passed
Softing Industrial Automation: OPC UA .NET Server Development Toolkits 1.43 2017-09 OPC Labs 2017.2 (5.51.0.7) Interoperability workshop Warning [29][11]
Systerel: S2OPC Demo Server 0.5.0* 2018-10 OPC Labs 5.54 (2018.3.0.33) Interoperability workshop Warning [30]
Takebishi: Device Gateway 2.1.2 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
Takebishi: DeviceXPlorer OPC Server 6.0 Pre 2018-10 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Passed [31][32]
Tani: OPC Server 1.7 2015-11 OPC Labs 5.36 Interoperability workshop Passed
Tani: OPC Server Linux 1.7 2015-11 OPC Labs 5.36 Interoperability workshop Passed [33]
Tani: PLC Engine Server raspberry 1.12 2016-11 OPC Labs 5.41 Interoperability workshop Failed [2]
Unified Automation: .NET based OPC UA Server SDK 2.4.0 2015-11 OPC Labs 5.36 Interoperability workshop Warning [34][11]
Unified Automation: C based OPC UA Server SDK 1.5.1 2015-11 OPC Labs 5.36 Interoperability workshop Warning [34]
Unified Automation: C++ based OPC UA Server SDK WINDOWS 1.5.0 2015-11 OPC Labs 5.36 Interoperability workshop Warning [34]
Unified Automation: High Performance OPC UA SDK 1.3.0 BETA 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Unified Automation: UA Gateway - connect classic OPC[35] 1.5.0 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
University of West Bohemia in Pilsen: OPC UA server for REX Control System 1.0.0 2015-11 OPC Labs 5.36 Interoperability workshop Passed
Yokogawa Electric Corporation: FAST/TOOLS OPC UA Server R10.04 SP1 2019-07 OPC Labs 2019.1 (5.55.0.3) Interoperability workshop Warning [36]
Yokogawa Electric Corporation: MDIS Demo Server 2020-03 OPC Labs 2020.2 (5.58.0.2) Interoperability workshop Passed [37]
Yokogawa Electric Corporation: opaf demo server 2019-03 OPC Labs 2019.1 (5.55.0.2) Interoperability workshop Passed
Yokogawa Electric Corporation: UA Server for CENTUM VP R1.02.10 2015-11 OPC Labs 5.36 Interoperability workshop Passed

OPC UA Global Discovery Services (GDS), Certificate Management (CM)

Other system model Other system version Test date Performed by This product version Test type Test outcome Notes
Microsoft: Azure IoT OPC Vault GDS Server private preview 2018-10 OPC Labs 2018.3 (5.54.0.33) Interoperability workshop Passed
OPC Foundation: UA .Net Standard Global Discovery Server 1.03.352.12 2018-09 OPC Labs 2018.3 (5.54.0.33) Developer Test Passed


More tests were performed, currently not explicitly listed here.

  1. do not know the HTTPS endpoint
  2. 2.0 2.1 getting BadIdentityTokenRejected from ActivateSession() with user identity = username/password
  3. the ServerDiagnostics.SessionDiagnosticsArray cannot be read with the credentials provided for testing
  4. server is revising publishing intervals to 0 and using its own
  5. 5.0 5.1 failed: reading and writing with IndexRange
  6. No dynamic nodes could have been tested.
  7. Empty ArrayDimensions instead of null returned with ValueRank=-2.
  8. DataChangeFilter=StatusValue does not prevent constant value with updating timestamps from being sent.
  9. 9.0 9.1 9.2 The SessionDiagnosticsArray node is missing, but the sessions are correctly available under SessionDiagnosticsSummary.
  10. Server sends data changes too fast.
  11. 11.0 11.1 11.2 Absolute Deadband filter: server sometimes sends notifications where the difference is less than the deadband
  12. HTTPS not supported by the server?
  13. Linux; driver-based
  14. reading Server_ServerDiagnostics_SessionsDiagnosticsSummary_SessionDiagnosticsArray (nsu=http://opcfoundation.org/UA/;i=3707) gives BadOutOfService
  15. reading ServerDiagnostics.SessionDiagnosticsArray gives BadNodeIdUnknown
  16. All nodes (even scalars from standard information model etc.) have ValueRank equal to -2 (Any): not compliant.
  17. The server returns ValuRank 0 for scalar nodes.
  18. GetEndpoints can return overloaded set of endpoints
  19. 19.0 19.1 Could not test much, server only has method calls support.
  20. 1) Effects of Writes with IndexRange are not sent through subscription. 2) Subscription ignores IndexRange. 3) After writing into an IndexRange, the whole array seems to be replaced when doing subsequent Read
  21. Sampling period 2000 ms, but receiving changes at around 1000 ms rate.
  22. Server sends changes too fast. I used sampling interval 2000 ms. The server has not revised it. But it has been sending notifications with average rate between 800-900 ms. I think it would be OK to send values faster than requested, but in that case the server should report the faster revised sampling rate properly to the client.
  23. Reading ArrayDimensions gives an array with zero elements. NodeID: ns=4;i=6013
  24. for S7-1500 family
  25. 25.0 25.1 no arrays available for testing
  26. sometimes getting just BadWaitingForInitialData and no further update
  27. Falcon appears to be a code name for upcoming version of dataFEED OPC Suite.
  28. Getting "Could not create SSL/TLS secure channel." with HTTPS endpoint; it is possible that the problem is on the client side.
  29. Writing with index range always gives BadIndexRangeInvalid
  30. There are nodes that have variable class, but return BadAttributeInvalid for the UserAccessLevel and Historizing attributes, which are mandatory.
  31. When the publishing rate was 1000 ms and sampling rate 2000 ms, the server provides changes every 1000 ms, which means it is sampling faster than requested.
  32. On subsequent connections after a network interruption, no initial update was sent for items that are static.
  33. values not changing
  34. 34.0 34.1 34.2 looks like LDS is not running
  35. based on Unified Automation C++ SDK
  36. Buggy NodeClassMask filtering in Browse service.
  37. Sample delivery approx. 50% slower than requested.