See also: QuickOPC Compatibility Test List (for Client/Server)
Introduction
See Compatibility Test Lists - Concepts.
Platform Hardware
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
PC, Intel Core i7-8550U CPU @ 1.80 GHz 1.99 GHz; 16.0 GB
|
|
2019-07
|
OPC Labs
|
2019.1 (5.55.0.3)
|
Interoperability workshop
|
Passed
|
W10/x64
|
Raspberry Pi Model 4; 4 GB
|
|
2021-01
|
OPC Labs
|
2021.1 (5.60)
|
Basic test
|
Passed
|
Raspbery Pi OS
|
More tests were performed, currently not explicitly listed here.
Operating Systems
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
Microsoft Windows 10 Pro
|
1803 x64 (English)
|
2019-07
|
OPC Labs
|
2019.1 (5.55.0.3)
|
Interoperability workshop
|
Passed
|
|
Raspberry Pi OS with desktop
|
2021-01-11
|
2021-01
|
OPC Labs
|
2021.1 (5.60)
|
Basic test
|
Passed
|
|
More tests were performed, currently not explicitly listed here.
.NET Runtimes
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
.NET
|
5.0.2
|
2021-01
|
OPC Labs
|
2021.1 (5.60.0.13)
|
Basic test
|
Passed
|
|
More tests were performed, currently not explicitly listed here.
OPC Publishers
UADP Messages over UDP Transport
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
Beckhoff Automation: TF6100 OPC-UA
|
?
|
2020-04
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Passed
|
[1]
|
Softing Industrial Automation: dataFEED OPC UA .NET Standard PubSub SDK
|
2.2
|
2019-07
|
OPC Labs
|
2019.1 (5.55.0.3)
|
Interoperability workshop
|
Passed
|
[2][3]
|
Softing Industrial Automation: OPC UA C++ Server Development Toolkits for Windows
|
5.60
|
2019-07
|
OPC Labs
|
2019.1 (5.55.0.3)
|
Interoperability workshop
|
Passed
|
[4]
|
Yokogawa Electric Corporation: UA Server for CENTUM VP
|
R1.05.00
|
2019-07
|
OPC Labs
|
2019.1 (5.55.0.3)
|
Interoperability workshop
|
Passed
|
[3]
|
JSON Messages over MQTT Transport
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
ICONICS GENESIS64
|
?
|
2021-04
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Passed
|
[5][6][7]
|
OPC Subscribers
Subscribers were tested with messages published by the UADemoPublisher.
UADP Messages over UDP Transport
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
Beckhoff Automation: TF6100 OPC-UA
|
?
|
2020-04
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Passed
|
[8]
|
JSON Messages over MQTT Transport
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
ICONICS GENESIS64
|
?
|
2021-04
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Passed
|
[7]
|
More tests were performed, currently not explicitly listed here.
PubSub Configuration Model
Other system model
|
Other system version
|
Test date
|
Performed by
|
This product version
|
Test type
|
Test outcome
|
Notes
|
Beckhoff Automation: TF6100 OPC-UA
|
?
|
2020-04
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Warning
|
[9][10]
|
Softing Industrial Automation: OPC UA C++ Server Development Toolkits for Windows
|
?
|
2019-07
|
OPC Labs
|
2021.2 (5.61.0.6)
|
Interoperability workshop
|
Passed
|
|
More tests were performed, currently not explicitly listed here.
Security Key Service
- ↑ Tests included chunked and secured messages (static keys).
- ↑ Subscriber UADP Periodic Fixed Layout Facet
- ↑ 3.0 3.1 Subscriber UADP Flexible Layout Facet
- ↑ Subscriber UADP Dynamic Data Facet
- ↑ MessageId is published as an integer, not a GUID.
- ↑ DataSetWriterId is published as a GUID, not a UInt16.
- ↑ 7.0 7.1 Capable of single message format only: NetworkMessageHeader == 1, DataSetMessageHeader == 1, SingleDataSetMessage == 0. Dataset fields are only encoded as in DataValue representation.
- ↑ A single simple test, with DataValue encoding.
- ↑ Publishing interval not properly exposed.
- ↑ Maximum string length not properly exposed.